Model 70200
Universal Oil Primary Control
Tech Support (800) 989-2275 www.carlincombustion.com
Installing and wiring
WarningThe 70200 control must be installed and serviced only by a qualied service technician.
1. Always disconnect power source before wiring to avoid electrical shock or damage to the control. All wiring must comply with applicable codes and
ordinances.
2. Thermostat terminals (T–T) provide a current source. Never apply external power to these terminals under any circumstances.
3. Alarm terminals provide a 24 VAC/VDC-rated dry contact, suitable for use with security/re alarm systems.
Mounting
• The control may be mounted on a 4” x 4” junction box in any convenient location on the burner, furnace or wall. The location must not exceed the ambient
temperature limit, 140°F.
Wiring
• Wiring must comply with local and national electrical codes, and with the wiring diagram.
Power input (red/white wire) 120 VAC, 60 HZ, 9VA
Limit circuit input
(black wire)) 120 VAC, 60 HZ
Motor load
(orange wire) 10 FLA/ 60 LRA (reduce by valve load)
Ignitor load (blue wire)) 120 VAC, 60 HZ, 500 VA
Vent Input 120 VAC, 60 HZ
Valve load 2 amps
Vent load 0.1 amp
Line Heater 1 amp
Alarm contacts (dry contacts) 24V, AC/DC, 2A
Operating temperature limits +32°F to +140°F
Storage temperature limits -40°F to +185°F
Thermostat anticipator current 0.1 A, AC
Agencies UL Recognized (US & Canada)
Replaces Carlin, Beckett, Honeywell and ICM
Primary Controls
On-Board LCD Screen no special tool needed
Valve delay on (0, 3, 10, 15, 30, 60, 120)
Trial for ignition time (15, 30, 45)
Motor Delay Off (0, 10, 15, 30, 120, 300, 900)
Interrupted duty or Smart Ignition operation
Early Spark Termination Timing (0, -5, -10)
• Smart Ignition
Number of recycles (0, 3, Unlimited)
Serviceman reset protection (3)
TT Option (jumpered or open)
Blocked vent protection
Dry set of Alarm contacts
Built-in Pump Prime
Provides cad cell reading in OHMS
Fault history records last 50 fault cycles,
easy to understand icons displayed on screen
for common failures, Valve, Motor, Ignitor
Programmable, Microprocessor Based, Universal Replacement for CAD Cell Oil Burner
Primary Controls
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - Model 70200

Model 70200 Universal Oil Primary Control Tech Support (800) 989-2275 www.carlincombustion.comInstalling and wiringWarning — The 70200 control must be

Seite 2 - Denitions:

© Copyright 2012 - Carlin Combustion Technology, Inc.Carlin part number MN70200 Rev. 02/24/14Programming and SetupDenitions:Valve Delay On: Time peri

Seite 3 - Operating and Fault History

Power ON Open all manual oil line valves. Close the line switch. Call for heat Set thermostat (and limit) to call for heat. Thermostat circuit

Seite 4 - Service & Troubleshooting

Service & TroubleshootingBurner (control) will not come onNo power to control • Check line voltage to the control (at least 102 vac). • Check